Published June 13, 2026
Transformer calculations look intimidating because there are several numbers flying around — FLA, turns ratio, OCPD — but each one answers a simple question. Here's what each piece means and how they fit together.
FLA tells you how much current the transformer draws (or delivers) at its rated KVA and voltage. The formulas:
The 1.732 (√3) factor accounts for the relationship between line and phase values in a three-phase system. You'll calculate FLA separately for the primary side (using primary voltage) and the secondary side (using secondary voltage) — same KVA, different voltage, different current.
The turns ratio is simply the primary voltage divided by the secondary voltage — it reflects the ratio of windings inside the transformer. A 480V-to-120V transformer has a turns ratio of 4:1. This is mostly a "sanity check" number — it confirms the transformer is doing what you expect (stepping voltage down or up by the expected amount) and can help verify nameplate data.
This is where a lot of the real-world decision-making happens. NEC Table 450.3(B) governs how the primary overcurrent protective device (breaker or fuse) is sized relative to the primary FLA.
For the common case of primary-only protection (no separate secondary OCPD) on transformers rated 1000V or less with primary current of 9A or more:
Worked example: a 75 KVA, 480V three-phase transformer has a primary FLA of 75,000 ÷ (480 × 1.732) ≈ 90.2A. 125% of that is ≈ 112.8A. Since 112.8A isn't a standard breaker size, round up to the next standard size — 125A.
Worth knowing: if a transformer has protection on both primary and secondary, NEC Table 450.3(B) allows the primary OCPD to go up to 250% of primary FLA — but that's a different scenario than the primary-only case most calculators (including ours) are built around.
Transformer sizing comes down to three questions: how much current flows on each side (FLA), what voltage relationship the windings create (turns ratio), and how big the primary breaker/fuse needs to be to protect the transformer without nuisance tripping on inrush (OCPD via 450.3(B)). Get those three numbers right, and the rest of the install follows naturally.
← Back to Blog